AL02 is a cooling system overload. The most common cause is a clogged air filter or condenser, especially in hot weather or on chillers that have run for a few years without cleaning.
Clear the alarm
Press and hold POW (or ENT on some units) for about 3 seconds. If the pump and compressor start and AL02 comes back shortly after, the chiller is not getting enough airflow.
Causes and what to check
- Dirty air filter or condenser. Remove the front filter and clean the filter and condenser fins with compressed air, cleaner and a soft brush. This fixes most AL02 alarms.
- Blown fan fuse. Check fuses F90 and F901 (2 A). Spare fuses are stored in the electrical box.
- Fan motor failure. If the fan does not spin, the motor winding may be burned out. Replace the fan motor.
- Damaged fan blade. A broken or unbalanced blade reduces airflow. Replace the fan.
- Compressor overload (F2) tripped. Check the setting and reset. If it trips again after cleaning, the compressor may be failing.
| Model | F2 overload setting |
|---|---|
| CIL301 | 4.6 A |
| CIL501 | 6.0 A |
| CIL751 | 11.5 A |
| CIL1101 | 12.5 A |
| CIL1501 | 15 A |
| CIL2201 | 18 A |
If contactor K2 stays engaged after the overload trips, the compressor needs replacing. Call us.
Parts for this alarm
- Air filter C630A26 (CIL301A-C, CIL501A-C)
- Air filter CL03M03 (CIL301A-CT, CIL501A-CT)
- Air filter C63046 (CIL751A-C)
- Air filter CL07M02A (CIL751A-CT)
- Air filter CL11M04A (CIL1101A-C)
- Air filter CL11M09 (CIL1101A-CT)
- Air filter CL15M05 (CIL1501A-CT)
- Air filter CL22M05 (CIL2201A)
- Condenser CL03M01B (CIL301, CIL501)
- Condenser CL07M11B (CIL751)
- Condenser CL11M10 (CIL1101)
- Condenser CL15M10 (CIL1501)
- Condenser CL22M01A (CIL2201)
- Fan motor assembly MT015002B (100 W)
- Fan motor assembly MT015200 (200 W)
- Fan Motor Assembly Set CL11FM01 (Doosan 210101-00429)
- Fan Motor Assembly Set CL07FM01 (Doosan 210101-00441)
- Fan Motor Assembly Set CL22FM01 (Doosan 210101-00212)
- Cooling Fan MA020013-1, 300 mm (Doosan 400206-00178B-11)
- Cooling Fan MA015350, 350 mm
Compressors, if the F2 overload keeps tripping after cleaning:
- Compressor CL0302002 (Doosan R90695C-11)
- Compressor CL0302001 (Doosan 400206-00319-03)
- Compressor CL0702001 (Doosan 400206-00193A-05)
- Compressor CL1102001 (Doosan 400206-00328-04)
- Compressor CL1502001 (Doosan 400206-00484-07)
- Compressor CL2202001 (Doosan 400206-00202-09)
Downloads
Still showing the alarm?
Call 847-466-5459 or email admin@industrynestparts.com with the alarm code, the chiller model and serial number from the nameplate, your machine model, and the supply voltage and frequency. If you can, press the PARA key and send us the parameter readings shown on the display. That lets us find the cause and the right part on the first call.
All Kwangrim alarm codes | Kwangrim manuals and drawings
These steps come from Kwangrim service documentation and apply to Kwangrim NANOCON CIL, CIC and CIW chillers. Turn off and lock out power before opening the chiller. Electrical and refrigeration work should be done by qualified technicians.